MTL4541A/AS current repeater 4/20mA passive i/p for HART® transmitters
MTL5541A provides an input for separately powered 4/20mA transmitters and also allows bi–directional transmission of HART communication signals superimposed on the 4/20mA loop current. Alternatively, MTL5541AS acts as a current sink for a safe-area connection rather than driving a current into the load.
SPECIFICATION FOR MTL5541A/AS
See also common specification
Number of channels
One
Location of transmitter
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div.1, Group A, hazardous location
Hazardous area input
Signal range: 4 to 20mA
Under/over-range: 1.0 to 21.5mA
Input impedance for HART signals
at terminals 1, 2: > 230Ω
Maximum input volt drop
at terminals 1, 2: < 6.6V
i.e. a transmitter load of 330Ω at 20mA
Safe-area output
Signal range: 4 to 20mA
Under/over-range: 1.0 to 21.5mA
Safe-area load resistance (MTLx541A)
Conventional transmitters: 0 to 360Ω
Smart transmitters: 250Ω ±10%
Safe-area load (MTLx541AS)
Current sink: 600Ω max.
Maximum voltage source: 24V DC
Safe-area circuit output resistance: > 1MΩ
Safe–area circuit ripple
< 50µA peak-to-peak up to 80kHz
Transfer accuracy at 20°c
Better than 20µA
Temperature drift
< 1µA/°C
Response time
Settles within 200µA of final value after 20ms
Communications supported
HART