Sales & Support: Request A Quote
Home ProductsMTL5500 Series Isolators

MTL5532 PULSE ISOLATOR PULSE & 4/20MA CURRENT OUTPUTS (IMPORTED WITH ORIGINAL PACKAGING)

MTL5532 PULSE ISOLATOR PULSE & 4/20MA CURRENT OUTPUTS (IMPORTED WITH ORIGINAL PACKAGING)

MTL5532 PULSE ISOLATOR PULSE & 4/20MA CURRENT OUTPUTS (IMPORTED WITH ORIGINAL PACKAGING)

Product Details:

Place of Origin: England
Brand Name: MTL
Certification: CE
Model Number: MTL5532

Payment & Shipping Terms:

Minimum Order Quantity: 10 pcs
Delivery Time: in stock
Payment Terms: T/T
Supply Ability: 500 pcs
Contact Now
Detailed Product Description

Kindly Note: For expanding further cooperation with customers, old and new, now we have MTL5544D, MTL5541 and MTL5511 barriers in stock with a special price.

If you have any need, kindly send an inquiry to us !

E-mail: info@mtl-barrier.com

MTL5532 PULSE ISOLATOR

MTL5532 isolates pulses from a switch, proximity detector, current pulse transmitter or voltage pulse transmitter located in a hazardous area. It is ideal for applications involving high pulse rates and fast response times, by repeating the pulses into the safe area. An analogue output proportional to frequency is also provided, together with a relay output, which may be configured to act as an alarm. Configuration is carried out with a personal computer.

SPECIFICATION

See also common specification

Number of channels

One, fully floating

Sensor type

Switch or proximity detector (NAMUR/BS EN 60947–5–6:2001)

2– or 3–wire voltage or pulse transmitter

Location of switch

Zone 0, IIC, T6 hazardous area

Div. 1, Group A, hazardous location

Location of proximity detector or transmitter

Zone 0, IIC, T4–T6 if suitably certified

Div.1, Group A, hazardous location

Input

Switch input:

Output ON if switch is closed

Proximity detector input:

Excitation: 7.0 to 9.0V dc from 1kΩ nominal

Output ON if input > 2.1mA* (< 2kΩ)

Output OFF if input < 1.2mA* (> 10kΩ)

Switching hysteresis: 0.2mA (650Ω) nominal

*NAMUR and BS EN 60947–5–6:2001standards

Current pulse input:

Transmitter supply: 16.5V dc at 20mA

Short circuit current: 24mA

Output: Iin > 9.0mA = ON, Iin < 7.0mA = OFF

Switching hysteresis: 0.5mA

Voltage pulse input

Input impedance: > 10kΩ

Switching point voltage (Vsp): 3, 6, or 12V nominal

(User selectable by switches on the side of the module)

Output: Vin > Vsp = ON, Vin < Vsp = OFF

Switching hysteresis: 100mV + (0.1 x Vsp) typical

Safe-area pulse output

Maximum delay: 10μs

Maximum off–state voltage: 35V

Maximum off–state leakage current: 10μA

Maximum on–state resistance: 25Ω

Maximum on–state current: 50mA

Output OFF if supply fails

Note: LFD signal is Zener-diode protected against inductive loads

Safe-area current output

Input capture delay: 2 signal periods (5ms min.)

Signal range: 4 to 20mA

Under/over range: 0 to 22mA

Load resistance: 0 to 450Ω @20mA

Output resistance: >1MΩ

Ripple: < 50μA peak-to-peak

Accuracy: better than 20μA at 20°C

Temperature drift: < 1μA/°C

Risetime (10% - 90%, after step change): 60 ms

Alarm output

Relay ON in alarm, 0.5A @ 35Vdc max.

 